The required specification of a surge protection device, to meet requirements of a particular application, depends on lightning threat parameters and the circuit in which it will be installed. The parameters are the result of extensive lightning research and show that lightning current amplitudes of 200kA are possible. In the case of a lightning strike on the outer protection device of a building these amplitudes may occur. In case a low voltage power supply is hit by such a strike the lightning current at the building entrance should be grounded. Given symmetrical current partitioning in the low voltage plant, as well as a current partitioning in the ratio 1:1, between the current entering the building and the discharge by the surge protection device, the result would be 25kA per phase with a 4-phase system. The lightning current impulse sets free enormous energies. Therefore indication of its amplitude, charge and specific energy quota are part of the standardisation. For calculations, the impulse form is generally indicated with (10/350) μs.
机译:为了满足特定应用的要求,电涌保护设备的规格要求取决于雷电威胁参数及其安装的电路。该参数是广泛的雷电研究的结果,表明雷电流电流幅值可能为200kA。在建筑物外部保护装置遭受雷击的情况下,可能会出现这些振幅。万一低压电源受到这种撞击,建筑物入口处的雷电流应接地。给定低压设备中的对称电流分配,以及以1:1的比例分配电流,在进入建筑物的电流与通过电涌保护装置进行的放电之间的分配,结果将是每相25kA(4相)系统。雷电流脉冲释放了巨大的能量。因此,指示其幅度,电荷和特定能量配额是标准化的一部分。为了进行计算,脉冲形式通常用(10/350)μs表示。