A dynamic simulation of a solar assisted cooling system has been carried out. System component modelling equations and parameters are given for the collector, flat plate heat exchanger, humidifier/evaporative cooler, sensible heat exchanger, desiccant bed/wheel, rockbed storage system, house load, and control systems. The computer program and its subroutine DESSYM are flowcharted. Results of simulations are given for College Station, El Paso, and Fort Worth, particularly including economic studies and analysis. Cooling systems are found to become economically feasible with plastic collectors having payback periods less than or equal to 12 years. A humidifier after cooling was found to be unnecessary. (ERA citation 08:009600)