首页> 美国政府科技报告 >Sandia Smart Anti-Islanding Project; Summer 2001: Task II Investigation of the Impact of Single-Phase Induction Machines in Islanded Loads: Summary of Results
【24h】

Sandia Smart Anti-Islanding Project; Summer 2001: Task II Investigation of the Impact of Single-Phase Induction Machines in Islanded Loads: Summary of Results

机译:桑迪亚智能反岛屿项目; 2001年夏季:任务II调查单相感应电机在以太载荷中的影响:结果总结

获取原文

摘要

Islanding, the supply of energy to a disconnected portion of the grid, is a phenomenon that could result in personnel hazard, interfere with reclosure, or damage hardware. Considerable effort has been expended on the development of IEEE 929, a document that defines unacceptable islanding and a method for evaluating energy sources. The worst expected loads for an islanded inverter are defined in IEEE 929 as being composed of passive resistance, inductance, and capacitance. However, a controversy continues concerning the possibility that a capacitively compensated, single-phase induction motor with a very lightly damped mechanical load having a large rotational inertia would be a significantly more difficult load to shed during an island. This report documents the result of a study that shows such a motor is not a more severe case, simply a special case of the RLC network.

著录项