首页> 外文会议>2000 International Conference on Power System Technology >Australian Snowy Mountains Hydro Scheme Earthing System Safety Assessment
【24h】

Australian Snowy Mountains Hydro Scheme Earthing System Safety Assessment

机译:澳大利亚雪山水电计划接地系统安全评估

获取原文

摘要

The task of determining the condition of the earthing in the Upper Tumut generation system, was undertaken as part of the Snowy Mountains Hydro Electric Authority's (SMHEA) safety risk assessment and asset condition monitoring programme. The testing programme to ascertain performance under earth fault and lightning conditions had to overcome considerable physical difficulties as well as the restrictions of 'close' proximity injection loops. The application of software, test instrumentation and testing procedures developed within Australia in collaboration between Energy Australia, Newcastle University, and SMHEA, to obtain real solutions are described in this paper. Also discussed are condition assessment processes that complement the current injection testing programme. This paper also provides a summary of the minimum requirements of an earthing system injection test to satisfactorily assess the condition of complex electrical power system installations.
机译:确定雪山山脉水电局(SMHEA)安全风险评估和资产状况监视计划的一部分,完成了确定上图穆特发电系统中接地状况的任务。确定接地故障和雷电条件下性能的测试程序必须克服相当大的物理困难以及“紧密”邻近注入回路的限制。本文描述了在澳大利亚能源公司,纽卡斯尔大学和SMHEA合作下在澳大利亚开发的软件,测试仪器和测试程序的应用,以获取实际的解决方案。还讨论了补充当前注射测试程序的状态评估过程。本文还概述了接地系统注入测试的最低要求,以令人满意地评估复杂的电力系统安装条件。