Comparative performance of impulsive grounding systems embedded in concrete: An experiment in reduced scale

机译:混凝土中脉冲接地系统的比较表现:减少规模的实验

获取原文

摘要

This paper presents a comparative study of impulsive grounding systems encased in concrete (namely UFER grounding). Several topologies used in transmission and distribution networks as well as in industrial plants were evaluated considering soils with different properties. Scale measurements (in an electrolytic tank with soil) were carried out in order to quantify the performance of this grounding system. The study discusses the performance of different grounding configurations: 1 rod; 2 rods; counterweight; cross and grid embedded in concrete. The results show that the use of UFER grounding can reduce significantly the value of the grounding impulsive impedance both in soils with low and high resistivity for the different evaluated configurations.
机译:本文介绍了混凝土中脉冲接地系统的比较研究(即UFER接地)。考虑具有不同性质的土壤,评估用于传输和分配网络以及工业植物中的几种拓扑。进行尺度测量(在具有土壤的电解槽中)进行,以量化该接地系统的性能。该研究讨论了不同接地配置的性能:1杆; 2杆;配重;嵌入混凝土中的十字架和栅格。结果表明,使用UFER接地的使用可以显着降低与不同评估配置的低和高电阻率的土壤中接地脉冲阻抗的值。