首页> 外文会议>International Conference on Lightning Protection >Melting and breaking of 80 mm2 OPGWs by DC arc discharge simulating lightning strike
【24h】

Melting and breaking of 80 mm2 OPGWs by DC arc discharge simulating lightning strike

机译:DC电弧放电模拟雷击的80 mm2 Opgws的熔化和断裂

获取原文

摘要

Metal strands of OPGWs (composite fiber-optic ground wires) are sometimes melted and broken by high-energy lightning strikes. DC arc tests simulating lightning strikes have thus been performed to obtain their melting and breaking characteristics. In this paper, to clarify the characteristics of thin OPGWs, experiments and calculations on the melting and breaking of 80 mm2 OPGWs were performed for different strand types (23AC, 30AC). The calculated dependence of the flowing electric charge required for three strands to break on the strand type shows good agreement with the experimental values obtained in DC arc tests simulating a lightning strike.
机译:OPGWS(复合光纤地面电线)的金属股有时被高能量雷击熔化和破碎。已经进行了模拟雷击掠过的直流电弧测试以获得它们的熔化和断裂特性。在本文中,为了阐明薄OPGWS的特性,对80mM2 OPGWS的熔化和分解的实验和计算是针对不同的股线(23ac,30ac)进行的。三条股中所需的流动电荷的计算依赖性在股线型上破裂,与模拟雷击的直流电弧试验中获得的实验值表现出良好的一致性。