The authors produced induced voltages on a real -size distribution line, the height of which is 10meters. A balloon filled with helium gas lifted a 150 meter-long copper conductor near the overhead distribution line. A pulse current was applied to the above conductor. Induced voltages on the overhead distribution line were observed at three points. As the distance between the grounding point of a copper wire and an overhead distribution line becomes large, the induced voltages on an overhead distribution line become small. The induced voltage is the largest at the nearest point to the balloon. As the distance from the nearest point to the balloon on the distribution line becomes large, the peak value of the induced voltage becomes small. Experimental results agree roughly well with calculated results obtained by a numerical analysis.
机译:作者在真实尺寸的分配线上产生了诱导电压,其高度为10米。填充氦气气体的气球升起了一个150米长的铜导线,靠近顶置配电线。将脉冲电流施加到上述导体上。在三个点观察到架空配电线上的诱导电压。随着铜线的接地点与架空分配线之间的距离变大,架空配电线上的感应电压变小。感应电压是最接近的球囊的最大电压。随着从分配线上的最近点到球囊的距离变大,诱导电压的峰值变小。实验结果对通过数值分析获得的计算结果非常好。