首页> 外文会议>International Conference on Electrical Machines and Systems >Improved Virtual Synchronous Generator Control of DFIG Under Symmetrical Drop of Grid Voltage
【24h】

Improved Virtual Synchronous Generator Control of DFIG Under Symmetrical Drop of Grid Voltage

机译:电网电压对称下降时双馈双馈发电机的改进虚拟同步发电机控制

获取原文

摘要

In order to optimize the frequency response characteristics of the wind power generation system, virtual synchronous generator (VSG) control is applied to doubly fed induction generator (DFIG). However, due to the slow dynamic response of original VSG control, rotor side converter cannot generate an appropriate regulated voltage quickly when the grid voltage occurs a symmetrical drop. To solve this problem, this paper proposes an improved control strategy. By introducing the rotor transient current control loop, the attenuation speed of stator transient flux is accelerated. At the same time, transient virtual resistance and SVPWM overmodulation limiting module are used to limit transient overcurrent and modulation overvoltage respectively. The simulation results validate the effectiveness of the proposed control method.
机译:为了优化风力发电系统的频率响应特性,将虚拟同步发电机(VSG)控制应用于双馈感应发电机(DFIG)。但是,由于原始VSG控制的动态响应较慢,因此当电网电压出现对称下降时,转子侧变流器无法快速生成适当的调节电压。为了解决这个问题,本文提出了一种改进的控制策略。通过引入转子瞬变电流控制回路,可以加快定子瞬变磁通的衰减速度。同时,使用瞬态虚拟电阻和SVPWM过调制限制模块分别限制瞬态过电流和调制过电压。仿真结果验证了所提控制方法的有效性。