In this paper is presented the development of a diagnosis system applied to high voltage (HV) energized grounding grids, based on the monitoring of the substation surface voltage potentials, to identify the localization of possible imperfections or defects (e.g. zones of high ohmic resistance, corrosion, discontinuity) in the grounding grid. It was developed an embedded electronic system capable to measure and process several surface voltages distributed throughout the grounding grid. After the data processing using the finite difference method, the system presents the grounding grid conditions using 2D graphs and numerical rapports. The analysis was performed based on the industrial voltage frequency
机译:本文提出了应用于高压(HV)通电接地网格的诊断系统的开发,基于对变电站表面电压电位的监测,以识别可能的缺陷或缺陷的定位(例如高欧姆电阻区域, 接地网格中的腐蚀,不连续性)。 它开发了一种能够测量和处理在整个接地网格中分布的多个表面电压的嵌入式电子系统。 在使用有限差分方法的数据处理之后,系统使用2D图和数值交流呈现接地网格条件。 基于工业电压频率进行分析