Due to the recent outbreaks of infectious diseases, such as severe acute respiratory syndrome (SARS), Influenza and Ebola, isolation facilities have played an important role to prevent infectious diseases from spreading at initial stage. An isolation ward is a facility to isolate patients physically and to care them safely. One way to isolate a patient physically is to build a negative pressure isolation facility. However, unexpected failure or misuse of such facility makes it difficult to maintain negative pressure and eventually causes secondary infection, leaking the infectious pathogen to outside of the isolation ward. This study identifies the amount and velocity of leakage air from a patient ward by tracer gas experiment under abnormal operations of an isolation facility. In addition, computational fluid dynamics (CFD) allowed us to observe the outflow mechanism of pollutant. The results show that abnormal operations of a facility spreads pathogens to neighboring areas immediately and timely actions should be prepared against them.
机译:由于最近的传染病爆发,如严重的急性呼吸综合征(SARS),流感和埃博拉,孤立设施发挥了重要作用,以防止传染病在初始阶段传播。一个隔离病房是一种孤立患者的设施,并安全地照顾它们。物理隔离患者的一种方法是构建负压隔离设施。然而,出乎意料的失败或滥用这种设施使得难以保持负压,最终导致继发感染,泄漏传染病物到隔离病房之外。本研究通过在隔离设施的异常操作下通过示踪气体实验识别患者病房的泄漏空气的量和速度。此外,计算流体动力学(CFD)允许我们观察污染物的流出机制。结果表明,应立即向其准备及时行动对邻近地区传播群体的异常运作。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号