The paper describes a study developed to estimate the energy savings potential of a radiant cooling system installed in an institutional building in Indonesia. The simulations were carried out using IESVE to evaluate thermal performance and energy consumption The building model was calibrated using the measured data for the installed radiant system. Then this calibrated model was used to simulate the energy consumption and temperature distribution to determine the proportional energy savings and occupant comfort under different systems. The result was radiant cooling which integrated with a Dedicated Outside Air System (DOAS) could make 41,84% energy savings compared to the installed cooling system. The Computational Fluid Dynamics (CFD) simulation showed that a radiant system integrated with DOAS provides superior human comfort than a radiant system integrated with Variable Air Volume (VAV). Percentage People Dissatisfied was kept below 10% using the proposed system.
机译:本文介绍了一项研究,该研究估算了在印度尼西亚的机构建筑中安装的辐射冷却系统的节能潜力。使用iEve进行模拟以评估热性能和能量消耗,使用所安装的辐射系统的测量数据进行校准建筑模型。然后,该校准模型用于模拟能量消耗和温度分布,以确定不同系统下的比例节能和乘员舒适性。结果是与专用外部空气系统(DOA)集成的辐射冷却,与安装的冷却系统相比,节能41,84%。计算流体动力学(CFD)仿真显示,与DOA集成的辐射系统提供优于具有与可变空气量(VAV)集成的辐射系统的人类舒适性。使用拟议的系统,不满意的人不满10%。