摘要

The effect analysis of strain rate on power transmission tower-line system under seismic excitation is studied in this paper. A three-dimensional finite element model of a transmission tower-line system is created based on a real project. Using theoretical analysis and numerical simulation, incremental dynamic analysis of the power transmission tower-line system is conducted to investigate the effect of strain rate on the nonlinear responses of the transmission tower and line. The results show that the effect of strain rate on the transmission tower generally decreases the maximum top displacements, but it would increase the maximum base shear forces, and thus it is necessary to consider the effect of strain rate on the seismic analysis of the transmission tower. The effect of strain rate could be ignored for the seismic analysis of the conductors and ground lines, but the responses of the ground lines considering strain rate effect are larger than those of the conductors. The results could provide a reference for the seismic design of the transmission tower-line system.
机译:研究了地震激励下应变率对输电塔线系统的影响。基于实际工程,建立了输电塔线系统的三维有限元模型。通过理论分析和数值模拟,对输电塔-线路系统进行了增量动力分析,以研究应变率对输电塔和线路非线性响应的影响。结果表明,应变率对输电塔的影响通常会减小最大塔顶位移,但会增加最大基础剪力,因此有必要考虑应变率对输电塔地震分析的影响。 。在进行导体和地线的地震分析时,可以忽略应变率的影响,但是考虑应变率效应的地线的响应要比导体的响应大。研究结果可为输电塔线系统的抗震设计提供参考。

著录项

  • 期刊名称 other
  • 作者

    Li Tian; Wenming Wang; Hui Qian;

  • 作者单位
  • 年(卷),期 -1(2014),-1
  • 年度 -1
  • 页码 314605
  • 总页数 10
  • 原文格式 PDF
  • 正文语种
  • 中图分类
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号