Development of HTS current leads for 1 kWh/1 MW module type SMES system. II. Manufacturing and testing of prototype leads

机译:开发用于1 kWh / 1 MW模块SMES系统的HTS电流引线。二。原型引线的制造和测试

获取原文
获取原文并翻译 | 示例
       

摘要

For pt.I see ibid., vol.7, no.2, p.684-7 (1997). We have been developing HTS current leads for a 1 kWh/1 MW module type SMES system (which we call "ESK" for Experimental SMES of Kyushu Electric Power Co., Inc.). Each module of a module type SMES system has a pair of current leads. For the purpose of reducing the heat load from the current leads, we have employed a bulk HTS. As a step in the preparation of HTS current leads for ESK, we trial produced HTS current leads and tested them to evaluate their characteristics. Our test results indicated that the heat load in a steady state at a rated current of 1 kA and with a rated flow rate of 0.05 g/s was 0.035 W, well below the specified value of 0.1 W. Also, our results indicated that the HTS current leads can be satisfactorily energized for pulsing operation at a rated current for ESK of 500 A-1 kA. The heat load under such conditions was 0.025 W, approximately 80% of that under normal 1 kA operating conditions. It was also verified that operation could be continued for 15 minutes even when the coolant flow was stopped.
机译:关于第一部分,见同上,第7卷,第2期,第684-7页(1997年)。我们一直在开发用于1 kWh / 1 MW模块型SMES系统(九州电力公司的实验SMES称为“ ESK”)的HTS电流引线。模块类型SMES系统的每个模块都有一对电流引线。为了减少电流引线的热负荷,我们采用了大体积HTS。作为准备用于ESK的HTS电流引线的一个步骤,我们试用了HTS电流引线并对其进行了测试以评估其特性。我们的测试结果表明,在额定电流为1 kA且额定流量为0.05 g / s的稳态下,热负荷为0.035 W,远低于规定值0.1W。此外,我们的结果还表明在500 A-1 kA的ESK的额定电流下,HTS电流引线可以令人满意地通电进行脉冲操作。在这种条件下的热负荷为0.025 W,约为正常1 kA工作条件下的热负荷的80%。还证实了即使冷却液停止流动也可以继续运行15分钟。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号