首页> 外文期刊>Energy Equipment and Systems >Analysis of effective factors on transient ground potential rise in gas insulated substations
【24h】

Analysis of effective factors on transient ground potential rise in gas insulated substations

机译:气体绝缘变电站暂态接地电位上升的影响因素分析

获取原文
           

摘要

This study presents the manner in which transient modeling concepts, which are fully analyzed in the referred standards, are implemented, for the purpose of evaluating the Transient Ground Potential Rise (TGPR). This is a phenomenon of 10–100kV voltages with up to 10μs duration on the grounded enclosure of Gas Insulated Substations (GIS), which may cause concern for personnel safety and problems for protection and control circuits in substations. This article summarizes the results of the investigation for influential factors on TGPR, such as, different contingency conditions and grounding system models. This article focuses on the TGPR study of "Siah-bishe" 400kV gas insulated substation. The study was carried out by modeling all pieces of equipment in the ElectroMagnetic Transients Program (EMTP)-RV, with careful consideration of different modeling guidelines and instructions described in the available standards.
机译:本研究介绍了在参考标准中进行了全面分析的瞬态建模概念的实施方式,目的是评估瞬态接地电位上升(TGPR)。这是在气体绝缘变电站(GIS)的接地外壳上持续10μs的持续时间的10–100kV电压现象,可能引起人员安全以及变电站的保护和控制电路问题。本文总结了对TGPR影响因素的调查结果,例如,不同的应急条件和接地系统模型。本文重点研究“ Siah-bishe” 400kV气体绝缘变电站的TGPR研究。通过对电磁暂态程序(EMTP)-RV中的所有设备建模,并仔细考虑了可用标准中描述的不同建模指南和说明,进行了研究。