首页> 外文期刊>Power Engineering Review, IEEE >Transient Ground Potential Rise in Gas Insulated Substation???Assessment of Shock Hazard
【24h】

Transient Ground Potential Rise in Gas Insulated Substation???Assessment of Shock Hazard

机译:气体绝缘变电站的瞬态地电位上升?冲击危险评估

获取原文
获取原文并翻译 | 示例
           

摘要

Breakdowns and disconnect switch operations in gas insulated switchgear (GIS) generate short duration high potentials on grounded GIS enclosures. These high potentials cause breakdowns between the GIS enclosures and other nearby grounded components, and have resulted in protection and control wiring failures and personnel shocks. The mechanism of the transient ground rise phenomenon and the equipment related problems are discussed in two companion papers. The question of the degree of personnel shock hazard imposed by transient ground rise is discussed in this paper. The physiological effects of short duration impulses are reviewed and it is concluded that further biomedical research is required.
机译:气体绝缘开关设备(GIS)的故障和断路开关操作会在接地的GIS外壳上产生短时的高电位。这些高电位可能会导致GIS机柜与附近其他接地组件之间发生故障,并导致保护和控制线路故障以及人员遭受电击。在两篇随附的论文中讨论了瞬态地面上升现象的机理以及与设备相关的问题。本文讨论了地面瞬时上升对人员造成电击危险的程度的问题。短时冲动的生理影响进行了审查,并得出结论,需要进一步的生物医学研究。