首页> 外文期刊>Electric power systems research >Harmonic behaviour of HVDC cables
【24h】

Harmonic behaviour of HVDC cables

机译:高压直流输电电缆的谐波行为

获取原文
获取原文并翻译 | 示例
           

摘要

The paper deals with harmonic analysis of HVDC submarine cables. The longitudinal series impedance matrix is computed with reference to armoured cables. The results are also compared with Finite Element models showing a very good agreement. This investigation can be considered the first step of more detailed further analysis about the propagation of harmonics on the d.c. and a.c. sides. Some novel matrix procedures are presented in order to pass from the loop impedance to the longitudinal series impedance matrix and to eliminate the grounded conductors. Comparisons with ATP-EMTP are not possible for a four metallic layered (core, screen, reinforcement and armour) HVDC cable since ATP-EMTP only takes three metallic layered cables into account.
机译:本文涉及高压直流海底电缆的谐波分析。纵向串联阻抗矩阵是根据铠装电缆计算的。还将结果与有限元模型进行比较,显示出很好的一致性。可以将这项研究视为对直流电上谐波传播进行更详细分析的第一步。和交流双方。为了从环路阻抗传递到纵向串联阻抗矩阵并消除接地导体,提出了一些新颖的矩阵程序。对于四层金属分层(芯,屏蔽,增强和铠装)HVDC电缆,无法与ATP-EMTP进行比较,因为ATP-EMTP仅考虑了三层金属分层电缆。