首页> 外文期刊>IEEE Transactions on Energy Conversion >Bus transfer of multiple induction motor loads in a 400 megawatt fossil power plant
【24h】

Bus transfer of multiple induction motor loads in a 400 megawatt fossil power plant

机译:400兆瓦化石电厂中的多个感应电动机负载的总线传输

获取原文
获取原文并翻译 | 示例
           

摘要

A computer model capable of simulating multiple induction motors during bus transfer is described and its results compared with field tests. Optimum switching times are specified based on bus residual voltage and phase angle that will maintain motor inrush currents below ANSI/NEMA criteria. Recent papers have documented the inadequacy of the ANSI/NEMA resultant V/Hz criteria for assuring that motor-shaft torques remain below acceptable levels following bus transfer. The presented results support these findings, but indicate that the combination of high and low-inertia motors fed from the same bus will reduce motor peak-shaft torques when compared to individual transfer of low-inertia motor/pump units alone.
机译:描述了一种能够在总线传输过程中模拟多个感应电动机的计算机模型,并将其结果与现场测试进行了比较。根据母线残余电压和相角指定最佳开关时间,以将电动机浪涌电流保持在ANSI / NEMA标准以下。最近的论文记录了ANSI / NEMA得出的V / Hz标准不足以确保总线传输后电动机轴扭矩保持在可接受的水平以下。给出的结果支持了这些发现,但表明与单独低惯性电动机/泵单元的单独传输相比,从同一总线馈送的高惯性电动机和低惯性电动机的组合将减少电动机峰值轴转矩。