Measurement of lightning surges originating from natural and rocket-triggered lightning strokes in winter has been carried out on a real-size test transmission line since 1987. During November 1993 to December 1995, fifteen flashes which struck the test transmission line were observed. In one of the fifteen cases, the arresters equipped on the test transmission tower operated and well controlled the voltages across the insulators. In another case, a four-phase back- flashover was observed on the upper and middle phases.
机译:自1987年以来,就已经在真实尺寸的测试传输线上进行了冬季冬季由自然和火箭触发的雷击产生的雷电浪涌的测量。在1993年11月至1995年12月期间,观察到了15次闪击测试传输线。在15种情况之一中,安装在测试传输塔上的避雷器可以操作并很好地控制绝缘子两端的电压。在另一种情况下,在上相和中相上观察到四相反闪络。