The EN 13565-2 fire fighting foam design standard came into force in 2009 but is still not as widely known as the long established NFPA 11 standard. However, early acquaintance is to be encouraged because the application rates for monitor application to tanks are considerably higher than under NFPA. For tanks of 45m to 60m diameter, the rate is 11 lpm/irf for 90 mins. and for 60m + tanks it is 12 lpm/m2 for 90 mins. Foam supplies will need to be considered either from the site itself or with neighbours with similar demands. Angus Fire, as the only UK manufacturer of foam, has a proven track record in supplying bulk stock by road tanker under police escort from its emergency stocks. The positioning of so called consignment stock needs to be carefully assessed as it may not be as readily available.
机译:EN 13565-2消防泡沫设计标准于2009年生效,但仍未像早已建立的NFPA 11标准那样广为人知。但是,应鼓励尽早相识,因为将监视器应用到储罐的应用率大大高于NFPA。对于直径为45m至60m的罐,速率为11 lpm / irf,持续90分钟。对于60m +的储罐,在90分钟内为12 lpm / m2。需要从现场本身或与需求相似的邻居一起考虑泡沫供应。安格斯消防公司(Angus Fire)是英国唯一的泡沫塑料生产商,在警方护送应急储存的护航下,在通过公路油轮提供大量储存方面拥有良好的记录。所谓寄售库存的位置需要仔细评估,因为它可能不容易获得。