Experimental investigations on adiabatic frictional pressure drops of R134a during flow in 5 mm diameter channel

机译:5 mm直径通道流动过程中R134a绝热摩擦压降的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

The article presents detailed two-phase adiabatic pressure drops data for refrigerant R134a at a saturation pressure of 5.5 bar corresponding to the saturation temperature of 19.4 degrees C. Study cases have been set for a mass flux varying from 100 to 500 kg/m(2) s. The frictional pressure drop was characterized for the refrigerant R134a, for vapor qualities ranging from 0 to 1. Long-time thermal stability of test facility allowed to gather a comprehensive experimental database for two-phase frictional pressure drop including multiple data points in transition and dryout flow regions. The effect of transition region on the peak value of two-phase frictional pressure drop, for literature models and experiment, is recognized.
机译:本文呈现详细的两相绝热压降用于在5.5巴的饱和度压力下对应于19.4摄氏度的饱和温度的饱和度压力下降的制冷剂R134a的数据。已经设定了从100至500kg / m的质量磁通量的研究病例(2 )s。 摩擦压降的特征在于制冷剂R134a,用于蒸汽品质范围为0至1.测试设施的长时间热稳定性允许为两相摩擦压降收集综合实验数据库,包括转换和干沟中的多个数据点 流量区域。 识别过渡区域对文学模型和实验的两相摩擦压降峰值的影响。