首页> 外文期刊>Materials at High Temperatures >Start-up issues with boiler water treatment and their solution
【24h】

Start-up issues with boiler water treatment and their solution

机译:锅炉水处理的启动问题及其解决方案

获取原文
获取原文并翻译 | 示例
           

摘要

The paper discussed the problems caused when dissolved oxygen was present in boiler makeup water. This could induce corrosion fatigue in feedheaters and economisers, in the temperature range 150-288 deg C. It could also lead to deposits that plugged tubes and led to turbine blade pitting.One of the serious issues in the cyclic operation of plants was the fact that deaeration was difficult after weekend start-ups, when there was a shortage of steam. Additions of hydrazine were not effective at this time, as water temperatures were too low.
机译:讨论了锅炉补给水中存在溶解氧时引起的问题。这可能会在150-288摄氏度的温度范围内在给水加热器和节能器中引起腐蚀疲劳。它还可能导致沉积物堵塞管子并导致涡轮机叶片出现点蚀现象。在缺乏蒸汽的情况下,周末启动后很难进行脱气。由于水温太低,此时添加肼无效。