首页> 美国政府科技报告 >Evaluating a Heptafluoropropane System With a Water Spray Cooling System for Compartments With Low Flash Point Liquids. Halon Replacement Agent Testing Compartment 1
【24h】

Evaluating a Heptafluoropropane System With a Water Spray Cooling System for Compartments With Low Flash Point Liquids. Halon Replacement Agent Testing Compartment 1

机译:用低喷点液体的水喷雾冷却系统评估七氟丙烷系统。哈龙替代剂测试室1

获取原文

摘要

As part of Halon 1301 replacement research, the Navy Technology Center for Safety and Survivability at the Naval Research Laboratory (NRL) has been investigating the use of HFP (heptafluoropropane, HFC-227ea, C(3)F(7)H) as a substitute in US Navy ship compartments. HFP has been shown to readily extinguish fires in a small-sized flammable liquid storage room. In the presence of fire HFP degrades into the extremely hazardous acid gas hydrogen fluoride (HF) in quantities significantly greater than those generated from Halon 1301 extinguished fires. The presence of HF in the room's atmosphere greatly hinders recovery. To counter the HF threat, we evaluated fire suppression via HFP with the NRL- invented Water Spray Cooling System (WSCS) in a 28 m(3) (1,000 ft(3)) simulated shipboard flammable liquid storage room. The objective of this test series was to quantify the benefit of using WSCS in conjunction with an HFP system. The resulting combined fire suppression system readily suppressed a fire while greatly reducing HF concentrations and cooling the compartment. The quantified benefits of WSCS were reduced temperatures, improved reignition protection, and reduced HF levels (by 75%), all allowing for enhanced safe compartment re-entry and recovery.

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号