首页> 外文会议>55th IWCS/Focus~TM Conference >Cable Material Component Effects On Large-Scale Fire Tests: Part 1
【24h】

Cable Material Component Effects On Large-Scale Fire Tests: Part 1

机译:电缆材料成分对大规模耐火测试的影响:第1部分

获取原文
获取原文并翻译 | 示例

摘要

In the first of a two part research study to understand the effects of cable material components on large-scale Steiner Tunnel test performance, twisted, 4-pair copper communications cables and respective cable jackets were evaluated for fire and smoke performance by ASTM El354 cone calorimeter. Data analysis indicates that inherent cable material properties (heat of combustion and smoke extinctional cross-sectional area) measured by small-scale cone calorimeter can be used as predictors for compliance to large-scale Steiner Tunnel test requirements set forth in NFPA 90A. Materials under study encompassed a broad range of tunnel fire and smoke performance.
机译:为了了解电缆材料成分对大型Steiner隧道测试性能的影响,该研究分为两部分,其中第一部分是通过ASTM El354锥形量热仪评估了4对双绞铜通信电缆和相应电缆护套的防火和防烟性能。数据分析表明,通过小规模锥形量热仪测得的固有电缆材料特性(燃烧热和烟的横截面积)可以用作满足NFPA 90A提出的大规模Steiner隧道测试要求的指标。研究中的材料涵盖了广泛的隧道防火和防烟性能。