首页> 外文会议>Information Science and Engineering (ICISE), 2009 >Failure Analysis of Transmission Tower under the Effect of Ice-Covered Power Transmission Line
【24h】

Failure Analysis of Transmission Tower under the Effect of Ice-Covered Power Transmission Line

机译:覆冰输电线路影响下的输电塔故障分析

获取原文

摘要

Ice storm is a kind of extreme weather conditions that can cause great losses to electric power system. The payments of power transmission towers account for 40 percent of total investment. For this, research on ultimate load and failure mechanism of transmission tower is very necessary. The property of ice coating is summarized in this paper. Also, the lateral load, the longitudinal load, and the vertical load of transmission tower under the effect of ice coating are discussed in detail. Taking a tangent tower as an example, finite element model is built with the consideration of beam element orientations. On these bases, the calculation of ultimate load capacity of the transmission tower is carried out in this paper. The results show that the mechanic behavior of transmission tower is similar to steel member, which can be approximately divided into three different stages: elastic stage, yield stage and strengthen stage.
机译:冰暴是一种极端的天气情况,会给电力系统造成巨大损失。输电塔的付款占总投资的40%。为此,研究输电塔的极限载荷和破坏机理十分必要。本文总结了冰涂层的特性。此外,还详细讨论了在覆冰作用下输电塔的侧向载荷,纵向载荷和竖向载荷。以切线塔为例,建立了考虑梁单元方向的有限元模型。在此基础上,对输电塔的极限承载力进行了计算。结果表明,输电塔的力学性能与钢构件相似,大致可分为三个阶段:弹性阶段,屈服阶段和加强阶段。