A fluoride tracer experiment was conducted to investigate mixing processes and residence times in a cylindrical clear water storage tank at the Stromlo Water Treatment Plant, Canberra, ACT. Four different modelling techniques have been used to simulate the experimental results: computational fluid dynamics (CFD), a single continuously stirred tank reactor (CSTR), two CSTRs in series, and a series/parallel combination of two CSTRs (NM). Flow of a conservative tracer through the tank has been simulated at the rated flow from the works using the PHOENICS (CFD) program. The CFD simulation agrees closely with the measured fluoride concentrations and requires no fitted parameters. The agreement with the experimental data for NM is comparable with the CFD and a little better than two CSTRs in series. The poorest agreement was obtained with a single CSTR model.
机译:进行了氟化物示踪剂实验,以研究在堪萨斯州堪培拉的斯特罗姆洛水处理厂的圆柱形净水储罐中的混合过程和停留时间。四种不同的建模技术已被用来模拟实验结果:计算流体动力学(CFD),单个连续搅拌釜反应器(CSTR),两个串联的CSTR和两个串联的CSTR(NM)。使用PHOENICS(CFD)程序以工作时的额定流量模拟了保守示踪剂通过储罐的流量。 CFD模拟与测得的氟化物浓度非常吻合,不需要合适的参数。与NM的实验数据的一致性与CFD相当,并且比两个串联的CSTR更好。最差的协议是使用单个CSTR模型获得的。