To extract copper, mines insert copper anodes into an electrolyte solution that is extremely acidic, with a pH of less than Stored in electrolytic cells as a blue fluid, the acidic solution creates significant loads. These loads are supported by a series of columns in the basement below the cell house. They serve as secondary containment for the electrolyte. Over the years, these support columns degrade and become susceptible to structural failure as the electrolyte leaks through the ceiling and into the column-to-beam connections. Exposure to electrolytes in the basement of the cell house causes the steel reinforcement within the concrete columns to corrode. Corrosion leads to oxidation in the columns. This creates an internal pressure that cracks the concrete. Corrosion of the reinforcing steel and delamination of the concrete shell causes structural degradation and failure of the columns.
机译:为了提取铜,矿山将铜阳极插入到极酸性的电解液中,该电解液的pH值小于190。作为一种蓝色液体存储在电解池中,酸性溶液会产生很大的负荷。这些载荷由地下室下方的一系列圆柱支撑。它们充当电解质的第二容器。多年来,随着电解质从顶棚泄漏到色谱柱与梁的连接处,这些支撑柱会退化并易于发生结构故障。暴露在电池室地下室中的电解质中会导致混凝土柱内的钢筋腐蚀。腐蚀导致色谱柱中的氧化。这会产生使混凝土破裂的内部压力。钢筋的腐蚀和混凝土壳体的分层会导致结构退化和圆柱破坏。